AFE EnclosureFan Testing ServiceAustralian Standards AS4214 - "Gaseous Fire Extinguishing Systems" and AS1851 - "Maintenance of Fire Protection Systems & Equipment" both require room integrity testing to be completed for "total flood" gaseous suppression system installations. Under these standards, room integrity is required to be tested initially as part of system commissioning, and then re-tested annually. Extinguishment Agent Retention - It's CriticalThe prime purpose of the room integrity test is to demonstrate how long a gaseous fi re extinguishing agent remains in the room following discharge of a "total flood" gaseous suppression system. The longer the gas remains after the discharge, the better the level of protection offered (AS4214 nominates a minimum retention time of 10 minutes). AFE can provide trained technicians and the necessary equipment to test the integrity of the rooms in which your suppression system is housed. A report shall be provided.
What the Standards Say!
|
| 2.38 Enclosure integrity | For total flooding systems where a fan unit can be fitted in the doorway: (a) COMPLETE a fan integrity test in accordance with AS4214 and confirm that the results satisfy the equirements of the original design. |
Yearly | Five Yearly |
Pressure Relief Venting
Integrity testing can also be used to predict the peak pressure likely to be experienced in the room during agent discharge. This is important to determine if the room is of sufficient strength to withstand the discharge pressure or if additional pressure relief venting is required. The correct operation of existing pressure relief vents can also be checked and the required size of additional pressure relief vents determined.
PASS/FAIL Enclosure Integrity Report

Clean Agent 2001 retention time prediction
| Building, Location | Complete Room |
| Company, Contact | Fire Safety Officer |
| Room Name | $ millions of risk Test number 1 |
| Certificate created | Date |
Typical Report Layout
| Test date/time: | |
| Tester: | |
| Signature: | ... |
| Maximum Protected Height, Ho: | 2.00m |
| Minimum Protected Height, H: | 1.20m |
| Elevation above sea level: | 4m |
| Correction method: | NFPA 2001(2000) |
| Initial concentration, C: | 7.70% |
| Mixing during retention: | No |
| Net protected volume, Vg: | 66m³ |
| Certified to Level: | No enclosure certification |
| Static during discharge, PSH: | 0/0 Pa |
| Operating temperature: | 21°C |
| Formula: | A-3-5.3.3 |
| Correction factor: | 0.99 |
| Agent: | FM200 (HFC227ea) |
| Agent quantity: | 5m³ |
| Actual total leakage, At: | 0.727m² |
| Actual lower leakage, Al: | 0.0364m² |
| Minimum concentration, Cmin: | 7.70% |
| Minimum retention time: | 10 min |
Note: Below ceiling leakage defaulting to worst case - 50% of total leakage
This enclosure was tested in compliance with ISO 14520.1 Annex E.
Assuming no continual mixing during the retention period, enclosure leakage could allow sufficient agent to be lost to cause an air/agent interface to descend from a Maximum Protected Height of 2.00m to the Minimum Protected Height specified of 1.20m.
The retention time would then be 8.9 minutes which is less than the minimum retention time of 10 minutes. The enclosure therefore FAILS this acceptance procedure.
Notes
Leakage of extinguishing gas may greatly reduce
the effectiveness of your gaseous fire suppression
system.
